TECHNICAL DATA
- Max. Operating Temperature: 90°C
- Max. Short Circuit Temperature: 250°C (max. 5 sec.)
- Rated Voltage: 6.35/11 kV (Um: 13.200V)
- Min. Bending Radius: 15x Cable Outer Diameter
- Production Standards: IEC 60502-2, VDE 0276-620, BS 6622
APPLICATION
These cables refer to XLPE insulated, PVC sheathed
ARMOURED Power cables with a rated voltage of
0,6/1 kV. These cables used for electricity supply in a low
voltage installation system. They are suitable for
installation indoors, outdoors, underground, in cables
ducts and power and switching stations, local energy
distributions, industrial plants, and places where is a risk of
mechanical damage. Due to having ARMOURED, these
cables can be used for heavy installation and mounting
conditions. They are also used under normal and salty water if
specially produced.
CONSTRUCTION
- Stranded Class 2 Copper or Aluminum Wire
- The inner layer of semi-conducting material
- XLPE Insulation
- The outer layer of semi-conducting material
- Semi-conducting tape
- The screen of copper wires
- Inner covering over laid-up cores
- Metallic Armour: Galvanised Steel Wires
- Outer sheath of Polyvinylchloride (PVC) or Polyethelene (PE)
SECTION RANGE
- For the Power Cables with Copper Conductor:
From 35mm2 up to 400mm2 - For the Power Cables with Aluminum Conductor:
From 35mm2 up to 400mm2
CODE of CABLE
- For the Cables with Copper Conductor:
Cu/XLPE/CTS/PVC/SWA/PVC; N2XSEYRY;
N2XSEYR(FL)2Y; YXC8VZ2V-R; YXC8VZ2(Q)2Y-R - For the Cables with Aluminum Conductor:
Al/XLPE/CTS/PVC/SWA/PVC; NA2XSEYRY;
NA2XSEYR(FL)2Y; YAXC8VZ2(A)V-R, YXC8VZ2(A)(Q)2Y-R
SPECIAL FEATURES
- Cables can be supplied with special flame retardant PVC or
Halogen Free Flame retardant(HFFR) outer sheath to
comply with the flame test requirements of IEC 60332
Category A-B and C upon special request. - Cables can be supplied with Polyethylene Outer Sheath
material upon special request. - Cables can be supplied with Longitudinally or
Radial+Longitudinally sealed watertight tape
(Swellable tape) upon special request