TECHNICAL DATA
- Max. Operating Temperature: 90°C
- Max. Short Circuit Temperature: 250°C (max. 5 sec.)
- Rated Voltage: 0,6/1kV (Um: 1200V)
- Min. Bending Radius: 15x Cable Outer Diameter
- Production Standard: IEC 60502-1; IEC60031; VDE
0276; HD 604; S1
APPLICATION
These cables refer to Mica Glass Tape +XLPE insulated,
HALOGEN FREE FLAME RETARDANT or LOW SMOKE
ZERO HALOGEN sheathed ARMOURED FE180 Power
Cables with a rated voltage of 0,6/1kV. These cables used in
energy networks in refineries, mines, hotels, schools, tunnels,
high constructions, hospitals, power plant, data processing
centers, business centers where there is a risk of fire and places
where is a risk of mechanical damage. Due to having ARMOUR
These cables can be used for heavy installation and mounting
conditions.
CONSTRUCTION
- Conductor: Stranded or Shaped Round Class 2
”Copper or Aluminium conductor” as per IEC 60228
For sections between 1.5mm2–10mm2; Solid Round Class 1
conductor can also be supplied upon request. - Insulation: Mica Glass Tape + XLPE insulation material.
Thickness shall be as per IEC 60502-1. - Inner Sheath/Filler: HFFR/LSZH Inner sheath
- Armour: Galvanised Round Steel Wire Armour or Double Steel
Tape Armour or Flat Steel Wire Armour + Steel Tape Armour
* For Single Core Cables Armour should be Aluminium Wire
Armour if the cable will not be used in DC System. - Outer Sheath: Halogen Free Flame Retardant or Low Smoke
Zero Halogen outer sheath material.
SECTION RANGE
- From 1.5 mm2 up to 630 mm2
CODE of CABLE
- Cu/MGT/ XLPE/SWA/HFFR; Cu/MGT/XLPE/DSTA/
HFFR; N2XRH FE 180; N2XFGbH FE 180; N2XBH FE
180; YXZ2H FE 180; YXZ3H FE 180; YXZ4H FE 180
CONDUCTOR QUANTITY
- For the Power Cables with Copper Conductor:
From 1 Core up to 5 Cores - For Control Cables with Copper Conductor:
From 5 Cores up to 48 Cores
COLOUR CODE of CABLE
- Insulation Colours code will be according to the
International Standards or customer’s request/demand.