TECHNICAL DATA

  • Max. Operating Temperature: 70°C
  • Max. Short Circuit Temperature: 160°C (max. 5 sec.)
  • Rated Voltage: 450/750V
  • Min. Bending Radius: 6x Cable Outer Diameter
  • Production Standards: IEC 60227, EN 50525-2-31
    HD 21.3 S3, VDE 0281, BS 6004

APPLICATION

These cables refer to PVC insulated Single Core Cables
Building Wire with a rated voltage of 450/750V. These cables
used for indoor fixed installations in dry locations,
in switchboards and distributors, installed in surface-mounted
or embedded conduits or flush-mounted in stationary plants,
dry places, distribution boards, and closed spaces like factories,
workshops, and any kind of workplaces.

CONSTRUCTION

  • Conductor: Solid Class 1 (Up to 10mm2 Section) or
    Stranded Class 2 Copper as per IEC 60228
  • Insulation: PVC insulation material
    *PVC Insulation material up to 90°C continuous operation
    also available upon special request.

SECTION RANGE

  • For Solid Class1 Copper Conductor:
    From 1.5mm2 up to 6mm2
  • For Stranded Class2 Copper Conductor:
    From 1.5mm2 up to 630mm2

CODE of CABLE

  • Cu/PVC; Conduit Wire; H07V-U; H07V-R; H07V2-R

Inquiry Form