TECHNICAL DATA
- Max. Operating Temperature: 70°C
- Rated Voltage: 300/500V
- Min. Bending Radius: 7.5x Cable Outer Diameter
- Production Standard: EN 50288-7
CONSTRUCTION
Conductor: Electrolytic, stranded, annealed plain copper wires to IEC 60228 Class 2 (Class 1 or Class 5 and/or tinned on request)
Insulation: PVC compound to EN50290-2-21
Black/White twisted pairs with numbered cores
Binder Tape: Polyester foil on each twisted pair
Individual Screen: Aluminium/polyester foil with a tinned copper drain wire in direct contact with the metallic side of the foil
Collective Screen: Aluminium/polyester foil with a tinned copper drain wire indirect contact with the metallic side of the foil
Outer Sheath: Flame retardant PVC compound to EN50290-2-22.
Blue for intrinsically safe cable, Black for UV resistant and/or non-intrinsically safe cable, Gray for indoor applications
CODE of CABLE
- CU/PVC/ISCR/OSCR/PVC; RE-Y(St)Y-fl PIMF
INTRODUCTION
These cables are used to link instruments and control systems
for analog or digital signal transmission in both indoor and
outdoor applications, petroleum refineries, petrochemistry
industry, power plants, natural gas pump stations, indoors and
outdoors, dry, damp and wet environments, gas stations, water
conveyance systems. Because these cables are not meant to be
used for power supply, they should not be connected directly to
the mains electrical supply or other low impedance
sources. When circuit integrity is essential in the event of a fire,
this product is recommended.
SECTION RANGE
- From 0.50mm2 up to 2.5mm2
CONDUCTOR QUANTITY
- From 2 pairs up to 50 pairs
COLOUR CODE of CABLE
- Insulation Colours code could be according to the
International Standards or customer’s request/demand.
* Other colours can be produced upon the customer
requests.