TECHNICAL DATA
- Max. Operating Temperature: 70°C
- Rated Voltage: 300/500V
- Min. Bending Radius: 8x Cable Outer Diameter
- Production Standard: EN 50288-7
CONSTRUCTION
Conductor: Electrolytic, stranded, annealed plain copper
Wires to IEC 60228 Class 2 (Class 1 or Class 5 and/or tinned
on request)
Insulation: PE-Polyethylene compound to EN50290-2-23
Binder Tape: Polyester foil on each twisted pair
Collective Screen: Aluminium/polyester foil with a tinned
copper drain Wire in direct contact with the metallic side of
the foil
Inner Sheath: PVC compound to EN50290-2-22
Armour: Wire braid armoured to EN 10257-1
Outer Sheath: Flame retardant PVC compound to EN50290-2-22.
Blue for intrinsically safe cable, Black for UV resistant and/or
non-intrinsically safe cable, Gray for indoor applications
CODE of CABLE
- CU/PE/OSCR/PVC/SWB/PVC;
RE-2Y(St)YSWBY-fl (MULTIPAIR)
INTRODUCTION
These cables used for connecting instruments and control
systems for analogue or digital signal transmission for indoor
and outdoor applications. These cables shall not be
connected directly to mains electricity supply or other low
impedance sources, since they are not designed to be used for
power supply.
SECTION RANGE
- From 0.50mm2 up to 2.5mm2
CONDUCTOR QUANTITY
- From 1 pair up to 50 pairs
COLOUR CODE of CABLE
- Insulation Colours code could be according to the
International Standards or customer’s request/demand.
* Other colours can be produced upon the customer
requests.