TECHNICAL DATA

  • Max. Operating Temperature: 90°C
  • Max. Short Circuit Temperature: 250°C (max. 5 sec.)
  • Rated Voltage: 0,6/1kV (Um: 1200V)
  • Min. Bending Radius: 15x Cable Outer Diameter
  • Production Standard: IEC 60502-1; IEC60031; VDE
    0276; HD 604; S1

APPLICATION

These cables refer to Mica Glass Tape +XLPE insulated,
HALOGEN FREE FLAME RETARDANT or LOW SMOKE
ZERO HALOGEN sheathed FE180 Power Cables with a rated
voltage of 0,6/1kV. These cables used in energy networks in
refineries, mines, hotels, schools, tunnels, high constructions,
hospitals, power plant, data processing centers, business centers
where there is a risk of fire.

CONSTRUCTION

  • Conductor: Stranded or Shaped Round Class 2
    Copper conductor
    *For sections between 1.5mm2–10mm2; Solid Round Class 1
    conductor can also be supplied upon request.
  • Insulation: Mica Glass Tape+, XLPE insulation material.
  • Inner Sheath/Filler: HFFR/LSZH Inner sheath
  • Outer Sheath: Halogen Free Flame Retardant or Low Smoke
    Zero Halogen outer sheath material. Thickness shall be as per
    IEC 60502-1.

SECTION RANGE

  • From 1.5 mm2 up to 630 mm2

CODE of CABLE

  • Cu/MGT/XLPE/HFFR FE180;
    Cu/MGT/XLPE/LSZHFE180; N2XH FE 180;
    YXH FE 180

CONDUCTOR QUANTITY

  • For the Power Cables with Copper Conductor:
    From 1 Core up to 5 Cores
  • For Control Cables with Copper Conductor:
    From 5 Cores up to 48 Cores

COLOUR CODE of CABLE

  • Insulation Colours code will be according to the
    International Standards or customer’s request/demand.