TECHNICAL DATA

  • Max. Operating Temperature: 70°C
  • Max. Short Circuit Temperature: (max. 5 sec.)
  • Cross section ≤ 300 mm2: 160°C
  • Cross section > 300 mm2: 140 °C
  • Rated Voltage: 0,6/1kV (Um: 1200V)
  • Min. Bending Radius: 15x Cable Outer Diameter
  • Production Standard: IEC 60502-1, VDE 0271

APPLICATION

These cables refer to PVC insulated, PVC sheathed armoured
power cables with a rated voltage of 0,6/1kV. These cables
used for electricity supply in a low voltage installation system.
They are suitable for installation indoors, outdoors,
underground, in cables ducts and power and switching
stations, local energy distributions, industrial plants, and
places where is a risk of mechanical damage. Due to having
ARMOUR, these cables can be used for heavy installation and
mounting conditions.

CONSTRUCTION

  • Conductor: Stranded or Shaped Round Class 2
    Aluminium conductor as per IEC 60228
    For sections between 1.5mm2 – 10mm2; Solid Round Class 1
    conductor can also be supplied upon request.
  • Insulation: PVC insulation material. Thickness shall be as per
    IEC 60502-1
  • Inner Sheath/Filler: PVC Inner sheath/Filler material.
  • Armour: Galvanized Round Steel Wire Armour or Double Steel
    Tape Armour or Flat Steel Wire Armour + Steel Tape Armour
    * For Single Core Cables Armour should be Aluminium Wire
    Armour if the cable will not be used in DC System.
  • Outer Sheath: PVC outer sheath material.

SECTION RANGE

  • From 10mm2 up to 630mm2

CODE of CABLE

  • Al/ PVC/SWA/PVC ; Al/ PVC/DSTA/PVC; NAYRY;
    NAYFGbY NAYBY; YAVZ2V; YAVZ3V; YAVZ4V

CONDUCTOR QUANTITY

  • From 1 Core up to 5 Cores

COLOUR CODE of CABLE

  • Insulation Colours code will be according to the
    International Standards or customer’s request/demand.

FIRE PERFORMANCE Of CABLE SHEATHS

  • Cables can be supplied with special flame retardant PVC
    outer sheath to comply with the flame test requirements of
    IEC 60332 Category A-B and C.

Inquiry Form