TECHNICAL DATA

  • Max. Operating Temperature: 90°C
  • Max. Short Circuit Temperature: 250°C (max. 5 sec.)
  • Rated Voltage: 0,6/1kV (Um: 1200V)
  • Min. Bending Radius: 15x Cable Outer Diameter
  • Production Standard: IEC 60502-1, VDE 0276
    HD 604 S1

APPLICATION

These cables refer to XLPE insulated, HALOGEN FEE
FLAME RETARDANT or LOW SMOKE ZERO HALOGEN
sheathed power cables with a rated voltage of 0,6/1kV.
These cables Used in energy networks in refineries, mines,
hotels, schools, tunnels, high constructions, hospitals, power
plant, data processing centers, business centers where there is
a risk of fire and places where is a risk of mechanical damage.
Due to having ARMOUR, these cables can be used for heavy
installation and mounting conditions.

CONSTRUCTION

  • Conductor: Stranded or Shaped Round Class 2 Aluminium
    conductor as per IEC 60228
    * For sections between 1.5mm2 – 10mm2; Solid Round Class 1
    conductor can also be supplied upon request.
  • Insulation: XLPE insulation material. Thickness shall be as per
    IEC 60502-1
  • Inner Sheath/Filler: HFFR/LSZH Inner Sheath/Filler Material
  • Armour: Galvanised Round Steel Wire Armour or Double Steel
    Tape Armour or Flat Steel Wire Armour and Steel Tape Armour
    * For Single Core Cables Armour should be Aluminium Wire
    Armour if the cable will not be used in DC System.
  • Outer Sheath: Halogen Free Flame Retardant or Low Smoke
    Zero Halogen outer sheath material. Thickness shall be as per
    IEC 60502-1

SECTION RANGE

  • From 10mm2 up to 630mm2

CODE of CABLE

  • Al/ XLPE/SWA/HFFR; Al/ XLPE/DSTA/HFFR;
    NA2XRH; NA2XFGbH; NA2XBH; YAXZ2H; YAXZ3H;
    YAXZ4H

CONDUCTOR QUANTITY

  • From 1 Core up to 5 Cores

COLOUR CODE of CABLE

  • Insulation Colours code will be according to the
    International Standards or customer’s request/demand.