TECHNICAL DATA
- Max. Operating Temperature: 90°C
- Max. Short Circuit Temperature: 250°C (max. 5 sec.)
- Rated Voltage: 0,6/1kV (Um: 1200V)
- Min. Bending Radius: 12x Cable Outer Diameter
- Production Standard: IEC 60502-1, VDE 0271, BS 7889
APPLICATION
These cables refer to XLPE insulated, PVC sheathed
power cables with a rated voltage of 0,6/1kV. These cables
used for electricity supply in a low voltage installation
system. They are suitable for installation indoors,
outdoors, underground, in cable ducts and power and
switching stations, local energy distributions, industrial plants,
and places where is no risk of mechanical damage.
CONSTRUCTION
- Conductor: Stranded or Shaped Round Class 2
Aluminium conductor as per IEC 60228
* For sections between 1.5mm2 – 10mm2; Solid Round Class 1
conductor can be also supplied upon request - Insulation: XLPE insulation material. Thickness shall be as per
IEC 60502-1. - Outer Sheath: PVC outer sheath material. Thickness shall be as
per IEC 60502-1.
SECTION RANGE
- From 10mm2 up to 630mm2
CODE of CABLE
- Al/XLPE/PVC; NA2XY; YAXV
CONDUCTOR QUANTITY
- From 1 Core up to 5 Cores
COLOUR CODE of CABLE
- Insulation Colours code will be according to the
International Standards or customer’s request/demand.
FIRE PERFORMANCE Of CABLE SHEATHS
- Cables can be supplied with special flame retardant PVC
outer sheath to comply with the flame test requirements of
IEC 60332 Category A-B and C.