TECHNICAL DATA

  • Max. Operating Temperature: 90°C
  • Max. Short Circuit Temperature: (max. 5 sec.) 200°C
  • Rated Voltage: 0,6/1kV
  • Min. Bending Radius: 6x Cable Outer Diameter
  • Production Standard: BS 6883, IEC 60092/353,
    IEC 60092/350-360, IEC 60332/1-2,
    IEC 60332/3-22 Cat A, IEC 60754 / 1-2,
    IEC 61034 / 1-2 (DIN EN 50268 / 1-2), IEC60811 /403

CONSTRUCTION

  • Conductor: Tinned stranded copper in accordance with IEC 60228 CL2, CL5
  • Mica Tape: Helically applied fire resistant tape
  • Insulation: Ethylene Propylene Rubber (EPR), GP4 in accordance with BS 7655-1.2
  • Tape: Polyester tape
  • Wire: Tinned copper drain wire
  • Tape: Polyester tape
  • Inner Jacket: Halogen free extruded compound, SW4 in accordance with BS 7655-2.6
  • Armour: Steel wire braid in accordance with BS 6883
  • Outer Jacket: Halogen free extruded compound, SW4 in accordance with BS 7655-2.6
  • Color: Black

CODE of CABLE

  • U-8RW4FRGT (I); CU/MGT/EPR/IS/SW4/GSWB/SW4

APPLICATION

These cables are used for fixed installation for power, control and lighting in both and safe areas, emergency and critical offshore applications where requirement for fire resistance exists.

SECTION RANGE

  • From 1mm2 up to 120mm2

CONDUCTOR QUANTITY

  • From 2 cores up to 37 cores

COLOUR CODE of CABLE

  • Insulation Colours code could be according to the
    International Standards or customer’s request/demand.
    * Other colours can be produced upon the customer
    requests.