TECHNICAL DATA
- Max. Operating Temperature: 90°C
- Max. Short Circuit Temperature: (max. 5 sec.) 250°C
- Rated Voltage: From 0,6/1kV up to 3,6/6kV
- Min. Bending Radius: 4x Cable Outer Diameter
- Production Standard: EN 50525-2-21, HD 22.4,
DIN VDE 0282-4, BS 6500, BS 7919, IEC 60245-4
CONSTRUCTION
- Conductor: Electrolytic Annealed, Class 2(NSGAOU) or
Class 5(NSGAF…) Stranded Plain Copper Wires - Screen: Tinned copper wires braiding for CMÖU Type
- Insulation: Special Elastomer compound
- Outer Sheath: HM3 Type Elastomer Compound
CODE of CABLE
- (N)SHXAÖ, (N)SHXAFÖ, (N)SHXAFCMÖ
APPLICATION
These cables are especially well-suited to short-circuit and
grounding connections. Rail vehicles, buses, switch cabinets,
continuously working installations, pipelines, and pipework
ducts, and dry interiors all employ them.
SECTION RANGE
- From 1mm2 up to 300mm2
CONDUCTOR QUANTITY
- These cables can be produced with single core
COLOUR CODE of CABLE
- Insulation Colours code could be according to the
International Standards or customer’s request/demand.
* Other colours can be produced upon the customer
requests.
FIRE PERFORMANCE of CABLE SHEATHS
Cables can be supplied with special flame-retardant PVC
outer sheath to comply with the flame test requirements of
IEC 60332 Category A-B and C.