TECHNICAL DATA
- Max. Operating Temperature: 70°C
- Max. Short Circuit Temperature: (max. 5 sec.)
- Cross section ≤ 300 mm2: 160°C
- Cross section > 300 mm2: 140 °C
- Rated Voltage: 0,6/1kV (Um: 1200V)
- Min. Bending Radius: 15x Cable Outer Diameter
- Production Standard: IEC 60502-1, VDE 0271
APPLICATION
These cables refer to PVC insulated, PVC sheathed armoured
power cables with a rated voltage of 0,6/1kV. These cables
used for electricity supply in a low voltage installation system.
They are suitable for installation indoors, outdoors,
underground, in cables ducts and power and switching
stations, local energy distributions, industrial plants, and
places where is a risk of mechanical damage. Due to having
ARMOUR, these cables can be used for heavy installation and
mounting conditions.
CONSTRUCTION
- Conductor: Stranded or Shaped Round Class 2
Copper conductor as per IEC 60228
For sections between 1.5mm2 – 10mm2; Solid Round Class 1
conductor can also be supplied upon request.
Insulation: PVC insulation material. Thickness shall be as per
IEC 60502-1 - Inner Sheath/Filler: PVC Inner sheath/Filler material.
- Armour: Galvanized Round Steel Wire Armour or Double Steel
Tape Armour or Flat Steel Wire Armour + Steel Tape Armour
* For Single Core Cables Armour should be Aluminium Wire
Armour if the cable will not be used in DC System.
Outer Sheath: PVC outer sheath material.
CODE of CABLE
- Cu/PVC/SWA/PVC; Cu/PVC/DSTA/PVC; NYRY;
NYFGbY; NYBY; YVZ2V; YVZ3V; YVZ4V
SECTION RANGE
- From 1.5mm2 up to 630mm2
CONDUCTOR QUANTITY
- For the Power Cables with Copper Conductor:
From 1 Core up to 5 Cores - For Control Cables with Copper Conductor:
From 5 Cores up to 48 Cores
COLOUR CODE of CABLE
- Insulation Colours code will be according to the
International Standards or customer’s request/demand.
FIRE PERFORMANCE Of CABLE SHEATHS
- Cables can be supplied with special flame retardant PVC
outer sheath to comply with the flame test requirements of
IEC 60332 Category A-B and C.