TECHNICAL DATA
- Max. Operating Temperature: 90°C
- Max. Short Circuit Temperature: 250°C (max. 5 sec.)
- Rated Voltage: 0,6/1kV (Um: 1200V)
- Min. Bending Radius: 15x Cable Outer Diameter
- Production Standard: IEC 60502-1, VDE 0276
HD 604 S1
APPLICATION
These cables refer to XLPE insulated, HALOGEN FEE
FLAME RETARDANT or LOW SMOKE ZERO
HALOGEN sheathed power cables with a rated voltage of
0,6/1 kV. These cables Used in energy networks in
refineries, mines, hotels, schools, tunnels, high
constructions, hospitals, power plant, data processing
centers, business centers where there is a risk of fire.
CONSTRUCTION
- Conductor: Stranded or Shaped Round Class 2 Copper
conductor as per IEC 60228
* For sections between 1.5mm2 – 10mm2; Solid Round Class 1
conductor can also be supplied upon request. - Insulation: XLPE insulation material. Thickness shall be as per
IEC 60502-1 - Inner Sheath/Filler: HFFR/LSZH Inner Sheath/Filler Material
- Armour: Galvanised Round Steel Wire Armour or Double Steel
Tape Armour or Flat Steel Wire Armour and Steel Tape Armour
* For Single Core Cables Armour should be Aluminium Wire
Armour if the cable will not be used in DC System. - Outer Sheath: Halogen Free Flame Retardant or Low Smoke
Zero Halogen outer sheath material. Thickness shall be as per
IEC 60502-1
SECTION RANGE
- From 1.5mm2 up to 630mm2
CODE of CABLE
- Cu/XLPE/SWA/HFFR; Cu/XLPE/DSTA/HFFR;
N2XRH; N2XFGbH; N2XBH; YXZ2H; YXZ3H; YXZ4H
CONDUCTOR QUANTITY
- For the Power Cables with Copper Conductor:
From 1 Core up to 5 Cores - For Control Cables with Copper Conductor:
From 5 Cores up to 48 Cores
COLOUR CODE of CABLE
- Insulation Colours code will be according to the
International Standards or customer’s request/demand.