TECHNICAL DATA
- Max. Operating Temperature: 90°C
- Max. Short Circuit Temperature: 250°C (max. 5 sec.)
- Rated Voltage: 0,6/1kV (Um: 1200V)
- Min. Bending Radius: 15x Cable Outer Diameter
- Production Standard: IEC 60502-1, VDE 0271, BS 5467
APPLICATION
These cables refer to XLPE insulated, PVC sheathed
ARMOURED Power cables with a rated voltage of 0,6/1kV.
These cables used for electricity supply in a low voltage
installation system. They are suitable for installation
indoors, outdoors, underground, in cable ducts and power and
switching stations, local energy distributions, industrial plants,
and places where is a risk of mechanical damage. Due to having
ARMOUR, these cables can be used for heavy installation
and mounting conditions.
CONSTRUCTION
- Conductor: Stranded or Shaped Round Class 2 Copper or
Aluminium conductor as per IEC 60228
* For sections between 1.5mm2 – 10mm2; Solid Round Class 1
conductor can be also supplied upon request - Insulation: XLPE insulation material. Thickness shall be as per
IEC 60502-1. - Outer Sheath: PVC outer sheath material. Thickness shall be as
per IEC 60502-1.
SECTION RANGE
- From 1.5mm2 up to 630mm2
CODE of CABLE
- Cu/ XLPE/SWA/PVC; Cu/ XLPE/DSTA/PVC; N2XRY;
N2XFGbY; N2XBY; YXZ2V; YXZ3V; YXZ4V
CONDUCTOR QUANTITY
- For the Power Cables with Copper Conductor:
From 1 Core up to 5 Cores - For Control Cables with Copper Conductor:
From 5 Cores up to 48 Cores
COLOUR CODE of CABLE
- Insulation Colours code will be according to the
International Standards or customer’s request/demand.
FIRE PERFORMANCE Of CABLE SHEATHS
- Cables can be supplied with special flame retardant PVC
outer sheath to comply with the flame test requirements of
IEC 60332 Category A-B and C.